Input Power
• Input voltage: 230 V~ 50/60 Hz
• 6 A maximum total input current
• At standby (no motors being driven), power is less than 1 W
• Lightning strike protection meets ANSI/IEEE standard 62.31-1980. Can withstand voltage surges of up to 6 000 V~ and current surges of up to 3 000 A
Output Capacity
• 1,5 A maximum motor load per channel (not for lighting control)
• Each zone supports only one motor; do not wire motors in parallel
• Raise and Lower outputs are mechanically interlocked to prevent simultaneously activating Raise/Lower outputs
• Designed to withstand 100 000 open/close cycles
Other Power Specifications
• Standby power: - 230 V~: 660 mW
• BTU/hour when fully loaded: 5
Environment
• Ambient temperature operating range (inside mounting panel): 0 ?C to 40 ?C (32 ?F to 104 ?F)
• Calibration point maximum: 65 ?C (149 ?F)
• Surrounding air temperature: Ta ? 65 ?C
• Relative humidity: less than 90% non-condensing
• For indoor use only
Terminals
• Mains Wiring: 1,0 to 4,0 mm2 (18 to 12 AWG)
• Zone Wiring: 1,0 to 4,0 mm2 (18 to 12 AWG)
• QS Link Wiring: See Wiring: QS Link
Mounting
• Use an IP20 (minimum) rated consumer panel or breaker panel with integrated DIN rail
• Width = 9 DIN modules (161,7 mm/6,4 in)
QS Link Limits
• A QS link can have up to 100 zones (outputs) and 100 devices
• Each motor control power module counts as 4 zones (outputs) and 1 device on the QS link
• The motor control power module (LQSE-4M-D) unit does not supply or consume power draw units. When using accessories (such as a keypad), an additional 24 V- power supply or a link power supply must provide power and/or power draw units For more information on Power Draw Units, see "Power Draw Units on the QS Link"