Switching Power Module
The DIN Power Module (DPM) family is a group of modular products for the control of lighting loads. This product is compatible with Lutron HomeWorks QS systems. This document describes the following product:
• LQSE-4S5-230-D: 4-zone power module for switching only.
Features
• Four switched output zones.
• Adaptive zero-cross switching maximizes relay life.
• Rated for lighting loads as defined by IEC/EN 60669 as well as INC, MLV, and ELV.
• Rated for motor loads of 1/2 HP.
• Includes QS link for seamless connection to a HomeWorks QS system.
• LEDs on the module provide diagnostic information.
• Buttons on module provide override control.
• Manual Override Contact Closure Input (CCI).
• Programmable Contact Closure Output (CCO).
• Power failure memory automatically returns the outputs to the levels they were set to prior to a power outage.
Power
• 220-240 V ~ 50/60 Hz
• Single input feed
• 16 A maximum input current
• Lightning strike protection meets ANSI/IEEE standard C62.41 and IEC 61000-4-5. Can withstand voltage surges up to 6000 V ~ and current surges up to 3000 A.
• ESD-protection exceeds agency requirements per IEC-61000-4-2
• For ungrounded delta feed applications, contact Lutron.
Output Zone Ratings
• Each zone is rated at 5 A for switching. Rated for resistive, inductive, or capacitive lighting loads as defined by IEC/EN 60669.
• Air gap off per output.
• No minimum load per output.
• This module is designed to control loads with ratings as noted in the table below.
• Outputs cannot be used to control general purpose receptacles.
• Special considerations:
– When controlling lamps, Lutron recommends using permanently installed fixtures.
– If controlling plug-in lamps, installation must ensure a method of preventing non-rated loads being plugged into the unit. An example is a dedicated receptacle with an alternate plug type.
– Controlling loads outside the parameters listed in the specifications may damage the device and void the warranty.
• If attempting to control general purpose receptacles, use the appropriate third-party power pack for the rated load.
• Run a separate neutral for each load circuit. A common neutral connection is not recommended.
• Unit may be powered by Ground Fault Interrupter (GFI) or Residual Current Circuit Breaker with Overload (RCBO) protected circuit if required.
QS Link Limits
• A QS link in a HomeWorks QS system can have up to 512 zones (outputs) and 100 devices (required HomeWorks QS processor counts as 1 device on the QS link).
• Each Switching Module counts as one device toward the 100 device limit, and 4 zones toward the 512 zone limit.
Mounting
• Mount in a Lutron DIN Panel (see specification sheet P/N 369788 at) or in an IP20 (minimum) rated consumer panel or breaker panel with integrated DIN rail.
• Unit is 9 DIN modules (161.7 mm [6.37 in]) wide.